Home / Product / Relay / Thermal Overload Relay
Parameter data sheet
| Product or Component Type | TeSys LRD;TeSys Deca |
| Product or Component Type | Differential thermal overload relay |
| Device short name | LRE13 |
| relay application | Motor protection |
| Product Compatibility | LC1E06-E38 |
| network type | AC |
| thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Signalling function | Relay trip indicator |
| Thermal protection adjustment range | 1…38 A |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Mechanical robustness | Shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7 Vibrations: 3 GN conforming to IEC 60068-2-6 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| [Ue] rated operational voltage | <= 690 V AC |
| Associated fuse rating | 10 A gG for power circuit 6 A aM for power circuit 5 A gG for signalling circuit |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Local signalling | Trip indicator |
| Control type | Push-button red stop: Push-button green reset: |
| Temperature compensation | -20…60 °C |
| Unit Type of Package 1 | PCE |
| Height*Width*Depth | 44.5 mm*45 mm*70 mm |
| Net Weight | 0.13KGS |